Amperage/Cord Power question
« on: July 06, 2015, 08:19 AM »
My knowledge of electrical is limited -- not much beyond the charts you find on the back of extension cord packaging telling you amp limits for specific cord lengths.

So at the jobsite I just moved into, the power situation is going to be pretty poor until we get someone in to do some work -- site hasn't been used in a few years, and currently I have one working outlet about 75 feet away from my work station, though it's run off a 20amp circuit.

I've run a 100 foot 10 gauge extension cord to draw power, but am wondering whether I might need to do another.  Here will be the basic load I'm putting: Kapex + CT, 1000 Watt worklight, and then the occasional reload of the PC portable air compressor.  There's also a portable fan and a Milwaukee radio/battery charger -- oh and a small fluorescent sign.  Given that the Kapex/CT and compressor draw will be intermittent (and will rarely, if ever, run at the same time), do you think I will be good on a single 100ft 10 gauge cord for right now?

Also, am I correct in assuming that the danger of tool motor degradation is not so much from overloading a circuit but rather when you use insufficient gauge cords to run power?
« Last Edit: July 06, 2015, 08:24 AM by Edward A Reno III »
Kapex KS 120 w/UG Cart and Extensions • CXS Set • T18+3 w/Centrotec Installer's Set • PDC 18/4 • TS 75 • TSC 55 • HKC 55 w/250, 420 and 670 FSK rails • Carvex 420 w/Accessory Kit • Domino 500 Set • Domino 700 XL • OF 2200 w/Base Accessory Kit • OF 1400 • OF 1010 • MFK 700 EQ Set • LR 32 • MFS 400 w/2000, 1000, and 700 extensions • Rotex 90 • Rotex 150 • LS 130 • ETS-EC 150/5 • ETS 150/3 • Pro 5 LTD • RTS 400 • RAS 115.04 • DX 93 • RS 2 • HL 850 • Vecturo OS 400 • CT 26 w/Long-Life Bag • CT Sys w/Long-Life Bag • MFT/3

Festool USA does not pre-approve the contents of this website nor endorse the application or use of any Festool product in any way other than in the manner described in the Festool Instruction Manual. To reduce the risk of serious injury and/or damage to your Festool product, always read, understand and follow all warnings and instructions in your Festool product's Instruction Manual. Although Festool strives for accuracy in the website material, the website may contain inaccuracies. Festool makes no representations about the accuracy, reliability, completeness or timeliness of the material on this website or about the results to be obtained from using the website. Festool and its affiliates cannot be responsible for improper postings or your reliance on the website's material. Your use of any material contained on this website is entirely at your own risk. The content contained on this site is provided for informational purposes only and does not constitute professional advice.


Offline SRSemenza

  • Global Moderator
  • *
  • Posts: 7993
  • Finger Lakes Region, NY State , USA
Re: Amperage/Cord Power question
« Reply #1 on: July 06, 2015, 09:05 AM »
  I think the 1000w work light is going to be the problem when on the same circuit as the rest. Is there something you can do to use a light with (much) lower wattage draw? You may need to turn the CT down to reduce draw. The 10ga  cord is a good call.

Seth

Offline Cheese

  • Posts: 3593
Re: Amperage/Cord Power question
« Reply #2 on: July 06, 2015, 11:35 AM »
As Seth said, the 1000 watt lighs will be an issue. I'd check into LED bulbs that replace the halogen light bulbs. They fit in the same space but cut the load to around 150 watts. You then also don't have the horrible/dangerous heat issues that you have with the halogens.

Offline jaguar36

  • Posts: 182
    • Toolamanjaro.com
Re: Amperage/Cord Power question
« Reply #3 on: July 06, 2015, 11:54 AM »
A 120V/20Amp circuit can only put out 16Amps continuous, which is about 1920 Watts. The Kapex can pull 1620 watts by itself (although that's not continuous).  At full speed the CT can pull 1200 Watts.  That means those two alone will take up pretty much the whole circuit.  Definitely will be a problem putting the 1000 watt light on the same circuit, and depending on how big the air compressor is, it could be a problem too. 

The 10 Gauge extension cord won't be an issue, the wires feeding the outlet are probably only 12 gauge.

Offline Cheese

  • Posts: 3593
Re: Amperage/Cord Power question
« Reply #4 on: July 06, 2015, 01:03 PM »
@Edward A Reno III
Bits & pieces: [2cents]
Festool recommends using a 10 gauge cord on the Kapex for distances of 50-100 feet. [thumbs up]
A 10 gauge cord is rated at 30 amps.  [thumbs up]
As @jaguar36 stated, a 20 amp breaker is derated to 16 amps (80%) for continuous (3 hours use) work. [crying]
A CT uses 2.9-10 amps. [big grin]
A Kapex can use up to 13 amps max.  [sad]
The 1000 watt halogens use 8.3 amps. [sad]
The 150 watt LED's use 1.25 amps. [thumbs up]
Most PC compressors are rated at 10 amps.  [sad]

So my take-away is, the Kapex and CT will work because they are intermittent. The compressor is also intermittent.
The halogens will be continuous and that's fine unless the compressor kicks in or you decide to use the Kapex. (I'd still change out the halogens for LED.) [big grin]
Run the Milwaukee radio on battery power and it's off the grid.
The portable fan (1 amp?) will also probably be ok, you just never know.

Is this 20 amp service on breakers of fuses? If fused, I'd suggest having a box or two of replacement fuses because things will happen.
« Last Edit: July 07, 2015, 08:31 AM by Cheese »

Offline ear3

  • Posts: 3344
Re: Amperage/Cord Power question
« Reply #5 on: July 06, 2015, 08:13 PM »
Thanks.  I decided just to hold off with the work light.  There is enough ambient light for the moment to do the first part of the set build -- especially since I only had to measure once at the beginning to set my stops and then just cut, cut, cut.  Hopefully they'll have the power situation figured out when I move to building the finer, trickier work, where I'll be measuring and fitting quite a bit.
Kapex KS 120 w/UG Cart and Extensions • CXS Set • T18+3 w/Centrotec Installer's Set • PDC 18/4 • TS 75 • TSC 55 • HKC 55 w/250, 420 and 670 FSK rails • Carvex 420 w/Accessory Kit • Domino 500 Set • Domino 700 XL • OF 2200 w/Base Accessory Kit • OF 1400 • OF 1010 • MFK 700 EQ Set • LR 32 • MFS 400 w/2000, 1000, and 700 extensions • Rotex 90 • Rotex 150 • LS 130 • ETS-EC 150/5 • ETS 150/3 • Pro 5 LTD • RTS 400 • RAS 115.04 • DX 93 • RS 2 • HL 850 • Vecturo OS 400 • CT 26 w/Long-Life Bag • CT Sys w/Long-Life Bag • MFT/3

Offline Chris Wong

  • Festool Dealer
  • *
  • Posts: 861
  • I make sculptural furniture.
    • Flair Woodworks
Re: Amperage/Cord Power question
« Reply #6 on: July 06, 2015, 11:18 PM »
The fluorescent sign piques my curiosity.  What kind of sign is it?
Chris Wong, http://FlairWoodworks.com

The thoughts and ideas expressed here are my own and do not necessarily represent those of http://UltimateTools.ca.  But Dan does say "hello".

Offline ear3

  • Posts: 3344
Re: Amperage/Cord Power question
« Reply #7 on: July 06, 2015, 11:40 PM »
6th pic down in first post:

http://festoolownersgroup.com/member-projects/film-setart-installation-build/


The fluorescent sign piques my curiosity.  What kind of sign is it?
Kapex KS 120 w/UG Cart and Extensions • CXS Set • T18+3 w/Centrotec Installer's Set • PDC 18/4 • TS 75 • TSC 55 • HKC 55 w/250, 420 and 670 FSK rails • Carvex 420 w/Accessory Kit • Domino 500 Set • Domino 700 XL • OF 2200 w/Base Accessory Kit • OF 1400 • OF 1010 • MFK 700 EQ Set • LR 32 • MFS 400 w/2000, 1000, and 700 extensions • Rotex 90 • Rotex 150 • LS 130 • ETS-EC 150/5 • ETS 150/3 • Pro 5 LTD • RTS 400 • RAS 115.04 • DX 93 • RS 2 • HL 850 • Vecturo OS 400 • CT 26 w/Long-Life Bag • CT Sys w/Long-Life Bag • MFT/3